Unités intérieures | AW-WHPMA18-H93 | AW-WHPMA22-H93 | AW-WHPMA26-H93 | AW-WHPMA30-H93 | |||
---|---|---|---|---|---|---|---|
Unités extérieures 1 ~230V - 50Hz |
— | — | — | — | |||
Unités extérieures 3 ~400V - 50Hz - N |
— | — | — | — | |||
Cooling | |||||||
Cooling::Operating limits | °C | -5/46 | -5/46 | -5/46 | -5/46 | ||
Cooling::Air 35°C - Water ind. 12°C /out. +7°C - Heating capacity | kW | 17 | 21 | 26 | 29.5 | ||
Cooling::Air 35°C - Water ind. 12°C /out. +7°C - Rated power input | kW | 5.57 | 7.12 | 9.63 | 11.57 | ||
Cooling::Air 35°C - Water ind. 12°C /out. +7°C - EER | 3.05 | 2.95 | 2.7 | 2.55 | |||
Cooling::Air 35°C - Water ind. 23°C /out. +18°C - Heating capacity | kW | 18.5 | 23 | 27 | 31 | ||
Cooling::Air 35°C - Water ind. 23°C /out. +18°C - Rated power input | kW | 3.9 | 5 | 6.28 | 7.75 | ||
Cooling::Air 35°C - Water ind. 23°C /out. +18°C - EER | 4.75 | 4.6 | 4.3 | 4 | |||
Indoor unit | |||||||
Outdoor unit::Airflow (LS/MS/HS/SS) | m³/h | 10650 | 10650 | 11200 | 11200 | ||
Outdoor unit::Dimensions (WxHxD) | mm | 1129x1558x440 | 1129x1558x440 | 1129x1558x440 | 1129x1558x440 | ||
Outdoor unit::Net Weight | kg | 177/206 | 177/206 | 177/206 | 177/206 | ||
Code | 7HP061085 | 7HP061086 | 7HP061087 | 7HP061088 | |||
Energy label | — | — | — | — | |||
Alimentation | |||||||
Alimentation::Phase/Voltage/Frequency | 3P/380-415V/50Hz | 3P/380-415V/50Hz | 3P/380-415V/50Hz | 3P/380-415V/50Hz | |||
Alimentation::Fuse rating am | A | 21 | 24.5 | 27 | 28.5 | ||
Actions | Request a quote | Request a quote | Request a quote | Request a quote |
Réf. : 7ACEL1882
Appareils : With this module you can simply manage 2 zones with 2 different temperatures (ex: floor heating & radiator). All the elements are pre-wired, you just have to plug them in on site. 1 Hydraulic module : - 2 water pump - 1 regulation - 2 thermostats (radio) - 1 outdoor temperature sensor (radio) - 1 antenna (for radio connection) Thermostat functions : - Change temperature (5°C to 37 °C) - Change mode (heating / cooling) - Weekly programming - Holiday mode
Réf. : 7ACFH0854
Appareils : To be use with the Bizone Kit. If you don't have buffer tank you can use this bottle. Easely paring with our Bizone Kit. Insulation included. 14 kW ∆T 5°C – 28 kW ∆T 10°C
Réf. : 7ACTL0510
Appareils : Helps reduce the transmission of vibrations. Length : 1 000mm
Réf. : 1PR070230
Appareils : Temperature sensor + wire (10m)
Réf. : 7ACFH0870
Appareils : Connection between temperature sensor and electronic board for balance tank probe
Réf. : 7ACFH0871
Appareils : Connection between temperature sensor and electronic board for solar probe
Réf. : 7ACEL1892
Appareils : Control the DHW electric heater with the heat pump
Réf. : 7ACFH0855
Appareils : 3 ways valve for heating and DHW
Réf. : 7ACFH0856
Appareils : Dirt separator,swiveling, with magnetic ring
Réf. : 7ACFH0857
Appareils : Ready to install Thermostatic valve Automatic opening (+ 3 ° C) and closing (+ 4 ° C) (+/- 1 ° C)
Réf. : 7ACFH0859
Appareils : Insulated bottle, reversible: heating and cooling ErP class: C Usable volume: 25 L Wall installation
Réf. : 7ACFH0858
Appareils : Insulated bottle, reversible: heating and cooling ErP class: C Usable volume: 51 L Wall installation
Réf. : 7ACFH0860
Appareils : Insulated bottle, reversible: heating and cooling ErP class: C Usable volume: 95 L Floor laying
Réf. : 7ACFH0861
Appareils : Insulated bottle, reversible: heating and cooling ErP class: C Usable volume: 195 L Floor laying
Réf. : 7ACFH0862
Appareils : Continuous evacuation of air (degassing) present in the hydraulic circuit Automatic operation Adjustable: horizontal or vertical mounting
Réf. : 7ACFH0863
Appareils : Plant power: 46 kW Graduated scale for adjustment: 0.1 to 0.6 bar differential
Réf. : 7ACFH0864
Appareils : CE standard vessel for heating and cooling circuit Capacity: 12 L Pre-inflation: 1 bar
Réf. : 7ACFH0865
Appareils : CE standard vessel for heating and cooling circuit Capacity: 18 L Pre-inflation: 1 bar
Réf. : 7ACFH0866
Appareils : Stem, vase support, equipped with: - quick coupling for vase - air vent ""PR2"" - NC valve with pressure gauge
Réf. : 7ACFH0867
Appareils : Non-controllable reduced pressure zone backflow preventer NF
Réf. : 7ACFH0868
Appareils : Low consumption electronic circulator (EEI <= 0.18) For heating and air conditioning With limescale protection during commissioning 5 year warranty Flow: 0.4 to 3.6 m3 / h Manometric head: 4 to 6.9 mWC 3 operating curves each with 3 speeds: - Proportional differential pressure - Constant differential pressure - Constant speed Protection class: IP X5
Réf. : 7ACFH0869
Appareils : Axial thermometer 0 / 120°